Distribution transformers - HVDC Convertor Package - Marinus Link
Tender ID: 613535
Tender Details
Tender Description
The auxiliary transformer systems will be used for supply of auxiliary power to
Station 1 Converter Station and Station 2 Converter Station, via the low voltage switchgear as ordinary auxiliary power sources.
Station 1 Converter Station Victoria (Hazelwood)
Station 2 Converter Station Tasmania (Heybridge)
Eight (8) distribution transformers are required, four (4) for Station 1 converter station and four (4) for Station 2 converter station.
Technical data:-
1. Type of transformer: Dry type, cast resin air insulated
2. Service conditions: Indoor
3. Rated power:1600 kVA
4. Rated voltages:22/0.4 kV
5. Rated frequency:50 Hz, 1 Hz
6. Short circuit impedance:6%.
7. Number of phases:3